Smoke fire damper
Fitted on the duct of a mechanical smoke extraction system. Normally open; in a fire it closes automatically at 280°C and may leak smoke, acting as a fire barrier.
Placement (on smoke ducts):
1. On the horizontal branch where a vertical duct meets each floor's horizontal duct.
2. On the smoke branch serving multiple smoke compartments.
3. At the smoke fan inlet.
4. Where it crosses a fire compartment.
Fire damper
Usually the 70°C fire damper: normally open, auto-closes in a fire, can be linked.
Placement (on ventilation and air-conditioning ducts):
1. Where it crosses a fire compartment.
2. Where it crosses the wall and floor of a ventilation or air-conditioning plant room.
3. Where it crosses the wall and floor of an important or high-fire-risk room.
4. On both sides of an expansion joint in a fire separation.
5. On the horizontal duct where a vertical duct meets each floor's horizontal duct.
Notes: 1. If each fire compartment has its own independent ventilation and air-conditioning system, the horizontal-to-vertical junction need not have a damper. 2. A kitchen exhaust duct uses a 150°C fire damper, closing automatically at 150°C.
Smoke valve
Fitted at the end of each branch (smoke intake) of a mechanical smoke system. Normally closed; opens manually or automatically in a fire and may leak air, serving smoke extraction.
Placement (on smoke ducts): at the end of each branch (smoke intake), usually at or near the ceiling.
Unlike the smoke fire damper, it has no 280°C fusible link — it only extracts smoke, with no fire barrier function.