In basement car parks fitted with a mechanical smoke extraction system, smoke fire dampers are placed at the following points as the code requires:
1. Where the duct passes through a firewall (fire compartment).
2. Where it passes through a ventilation or air-conditioning plant room.
3. At each floor's horizontal main duct where it meets the vertical main.
4. On both sides of an expansion joint.
Consider a specific ventilation system. The supply fan in a basement car park should have a motorised volume damper or a fire control damper (auto-close at 70°C) at the outlet duct where it crosses the plant-room firewall. If the supply system is shared with the fire mechanical make-up air system, use a motorised volume damper that auto-closes at 280°C. For the fresh-air intake, judge each case: a supply fan drawing fresh air directly from outside (single-level basement) may omit the damper at the intake; when several supply fans share one plant room, fit a check valve at each fan intake. For a multi-level basement using a shared fresh-air shaft, fit a fire damper or fire control damper (auto-close at 70°C) at each supply fan intake.
Supply and exhaust ducts should not pass through firewalls or non-combustible floors. When they must, fit a 70°C fusible-link smoke fire damper at the crossing. When fire smoke reaches the barrier, the damper shuts at once. This motorised volume damper is normally controlled by a smoke detector rather than a fusible link or element, so it stops the fire from spreading promptly and effectively.