The data below are one selection example; the unit is built to order by airflow.
Data sheet for the dry chemical filtration module/unit:
Equipment name | Fresh-air chemical filtration unit | |||
Tag number | Dry chemical filter casing module | Quantity | 1 | |
Brand | Keruite | Dimensions | 1500x1200x1200 mm (H) | |
Pre-filter | Filter class | G4 | Media | Non-woven fabric |
Filtration efficiency | 30%, initial resistance 30 Pa | Differential pressure gauge | 1 | |
Chemical stage I | Media | M9000C | Active ingredient | Impregnated activated carbon, potassium hydroxide |
Filtration efficiency | ≥99.5% | Pressure loss (Pa) | 100 | |
Media weight | 1 set | - | - | |
Chemical stage II | Media | M1000C | Active ingredient | Impregnated alumina, potassium permanganate |
Filtration efficiency | ≥99.5% | Pressure loss (Pa) | 100 | |
Media weight | 1 set | - | - | |
Medium filter | Filter class | F7 | Media | Glass fibre |
Filtration efficiency | 99% | Differential pressure gauge | 1 | |
Fan section | Airflow (m³/h) | 2200-8000 m³/h | Fan type | Direct drive |
Motor power (kW) | ≤3 kW | Brand | Keruite | |
Motor brand | Jinlite | Motor protection | Class F, IP55 | |
Casing | Material | Carbon steel plate, inner and outer sheet ≥0.5 mm | Insulation | ≥30 mm polyurethane |
Air leakage | Unit leakage <0.9% at design pressure | - | - | |
Connections | Size (mmxmm) | 630x500 | Other | Motorised control valve |
Control | Motor overload, overheat, short-circuit and phase-loss protection; manual/auto switch for the fan; run-status display and fault alarm. One run-status signal (passive dry contact), one general fault-alarm signal (passive dry contact), one fire-interlock interface (passive dry contact), one hazardous-gas alarm interlock (passive dry contact). |
Manufacturer: Keruite Air Conditioning Group Co., Ltd.