WhatsApp 中文 Русский
Keruite fresh-air chemical filtration unit: data sheet

Data sheet for the Keruite fresh-air chemical filtration unit: pre-filter, two chemical stages, medium filter, fan and motor ratings, casing, leakage and control interfaces listed.

The data below are one selection example; the unit is built to order by airflow.

Data sheet for the dry chemical filtration module/unit:

Equipment name

Fresh-air chemical filtration unit

Tag number

Dry chemical filter casing module

Quantity

1

Brand

Keruite

Dimensions

1500x1200x1200 mm (H)

Pre-filter

Filter class

G4

Media

Non-woven fabric

Filtration efficiency

30%, initial resistance 30 Pa

Differential pressure gauge

1

Chemical stage I

Media

M9000C

Active ingredient

Impregnated activated carbon, potassium hydroxide

Filtration efficiency

≥99.5%

Pressure loss (Pa)

100

Media weight

1 set

-

-

Chemical stage II

Media

M1000C

Active ingredient

Impregnated alumina, potassium permanganate

Filtration efficiency

≥99.5%

Pressure loss (Pa)

100

Media weight

1 set

-

-

Medium filter

Filter class

F7

Media

Glass fibre

Filtration efficiency

99%

Differential pressure gauge

1

Fan section

Airflow (m³/h)

2200-8000 m³/h

Fan type

Direct drive

Motor power (kW)

≤3 kW

Brand

Keruite

Motor brand

Jinlite

Motor protection

Class F, IP55

Casing

Material

Carbon steel plate, inner and outer sheet ≥0.5 mm

Insulation

≥30 mm polyurethane

Air leakage

Unit leakage <0.9% at design pressure

-

-

Connections

Size (mmxmm)

630x500

Other

Motorised control valve

Control

Motor overload, overheat, short-circuit and phase-loss protection; manual/auto switch for the fan; run-status display and fault alarm. One run-status signal (passive dry contact), one general fault-alarm signal (passive dry contact), one fire-interlock interface (passive dry contact), one hazardous-gas alarm interlock (passive dry contact).

Manufacturer: Keruite Air Conditioning Group Co., Ltd.

K
KRT Engineering Team
Technical Reviewed by Keruite HVAC Engineering Team

This article has been reviewed by our engineering team with 30+ years of HVAC manufacturing experience. For technical questions, contact us via the inquiry form.

Learn more about our team →
Share this article: