A fire damper sits in the supply and return ducts of a ventilation or air-conditioning system. It stays open during normal operation. When a fire raises the duct gas temperature to 70°C, the damper closes automatically. It then holds its fire stability and integrity for a set time, blocking smoke and fire spread. A smoke damper sits in the smoke extraction duct or at the fan inlet. It stays closed normally. On a fire alarm it opens manually or automatically, works with the system to extract smoke, and closes at 280°C to keep blocking smoke and fire.
Code basis
GB 50016-2006 (China's Code for Fire Protection Design of Buildings) sets the rules for fire damper placement.
Fit fire and smoke dampers (openings) in the correct direction and position. Where a fire damper sits on both sides of a fire compartment wall, it must be no more than 200 mm from the wall surface.
Layout considerations
A fire damper's position is fixed by two facts: it sits at the fire compartment, and within 200 mm of the wall. The plant room size decides whether a silencer can be installed inside it; from a noise viewpoint, inside the plant room is best.
Overview
The name says it: a fire damper blocks smoke and flames from a fire zone and keeps its fire stability and integrity for a set time. Fire spreads fast along ventilation and air-conditioning ducts, causing major loss. Good fire and smoke control limits that spread, so correct damper selection and placement matter.
Structure and working principle
A fire damper (Fig. 1) has a body and an actuator. The body has a casing, flange, blades and a blade linkage. The actuator has a housing, a blade-adjustment mechanism, a clutch and a thermal fuse. The actuator uses a metal fusible link and clutch to turn the blades. When the gas reaches the fuse's melt temperature, the link breaks. A spring drives the clutch plate off, releasing the blade mechanism. Two torsion springs then turn the blades shut. The actuator is purely mechanical, needing no power, so it works in any condition. It stays open during normal running and shuts only when the temperature passes the set point.
Types and performance
| Name | Application | Features | Actuator |
|---|---|---|---|
| Fire damper | In HVAC ducts, stops fire spread along ducts | 1. Auto-closes at 70°C, fan stops (FD) 2. Manual close, fan stops 3. Sends closed signal | FD |
| Fire control damper | In HVAC ducts, stops fire spread | 1. Auto-closes at 70°C, fan stops (FVD) 2. Manual close, fan stops 3. Airflow adjustable in 5 steps, 0°–90° 4. Sends closed signal | FVD |
| Smoke control damper | On ducts with smoke-control needs | 1. Smoke detector closes it electrically (smoke control), fan stops (SFVD) 2. Auto-closes at 70°C (fire), fan stops 3. Manual close, fan stops 4. Airflow adjustable in 5 steps, 0°–90° 5. Sends closed signal | SFVD |
| Remote smoke control damper | On ducts with smoke-control needs; for complex layouts needing frequent adjustment | 1. Smoke detector closes it electrically (smoke control), fan stops (BSFVD) 2. Auto-closes at 70°C (fire), fan stops 3. Remote manual close, fan stops 4. Airflow adjustable in 5 steps, 0°–90° 5. Sends closed signal | BSFVD |
| Smoke fire damper | On smoke extraction and fire-protected ducts, at the fan inlet… | - | - |