System Strategy
Prefer a fresh-air pre-treatment scheme: a dedicated outdoor unit with strong dehumidification controls humidity, while circulation units handle temperature — delivering high precision and energy savings. Size circulation units (1-to-1 up to 1-to-3) by cleanroom grade and simultaneous usage.
Filtration & Control
- Circulation units: secondary or intermediate filtration plus terminal HEPA; outdoor units: three-stage filtration to protect downstream filters.
- Use VAV control where possible to keep supply and fresh-air volumes constant.
- Ensure smooth drainage, built-in disinfection and positive-pressure design.
Key Details
- Outdoor units need three-stage filtration, dehumidification and coil freeze protection.
- Humidify in circulation units with isothermal steam, not adiabatic sprays.
- Reheat via hot water or heat recovery; size cooling by supply dew point and room load, distinguishing unit cooling capacity from supplied air cooling.
- DX system design differs fundamentally from comfort-air conditioning.