WhatsApp 中文 Русский
Procurement specs for hygienic combined AHU AHU-403

Technical procurement parameters for the hygienic combined air-handling unit AHU-403: airflow, loads, sections, filtration and noise limit.

1. Name: hygienic combined air-handling unit AHU-403.

2. Model: mechanically circulated four-pipe system.

3. Specification: airflow ≥14500 m³/h, cooling load ≥43 kW, heating load ≥34 kW, motor power ≥11 kW.

4. Mounting: floor-standing.

5. Dampers and supports: rubber damping for the unit, spring damping for the fan.

6. Sections: mixing + fan + flow equalising + primary and secondary filtration (G4, F8) + cooling coil + heating coil + humidification + supply + drain pan.

7. Fitted with inspection light and disinfection device.

8. Unit installation, commissioning and trial run.

9. Use a direct-drive plenum fan or centrifugal fan with VFD control; coils use quality copper tube with anti-corrosion hydrophilic aluminium fins; the condensate pan is a stainless steel dry pan.

10. Panel insulation uses non-combustible rock wool, density ≥80 kg/m³, or PTS high-strength foam board. Top and side panels ≥50 mm, base ≥50 mm.

11. The unit must be quiet: noise measured 2 m away ≤60 dB(A).

K
KRT Engineering Team
Technical Reviewed by Keruite HVAC Engineering Team

This article has been reviewed by our engineering team with 30+ years of HVAC manufacturing experience. For technical questions, contact us via the inquiry form.

Learn more about our team →
Share this article:
← T35-11 axial ventilation fan: model and specifications Textile market update in 5 Key Aspects You Should Know →