These dampers are generally placed where ventilation and air-conditioning ducts cross a fire compartment. They stay open normally and close in a fire to stop smoke and flame spreading along the duct to other compartments. They fall into three classes:
1. A 3C fire damper driven by a thermal fuse in the body. The fuse's melt temperature is 70°C; this type is the most used. Note: fit the thermal fuse facing the airflow. When the 3C fire damper also regulates flow, it is called a fire control damper.
2. A 3C fire damper linked to a temperature sensor in the ceiling. This type sees little use in China.
3. A 3C fire damper linked to a smoke sensor in the ceiling. This type is often called a smoke control damper.
Where a project needs both, a 3C fire damper may carry both a thermal fuse and a smoke sensor link; such a valve is called a smoke-control 3C fire damper.
In combined systems, a duct may have an exhaust outlet on the main. During smoke extraction that outlet must close; a fire damper combined with a louver outlet, called a fire outlet, serves this.