3C smoke fire damper: basic classification

A 3C smoke fire damper sits where ventilation ducts cross fire compartments. This article covers its three basic types by fuse, sensor and combined action.

These dampers are generally placed where ventilation and air-conditioning ducts cross a fire compartment. They stay open normally and close in a fire to stop smoke and flame spreading along the duct to other compartments. They fall into three classes:

1. A 3C fire damper driven by a thermal fuse in the body. The fuse's melt temperature is 70°C; this type is the most used. Note: fit the thermal fuse facing the airflow. When the 3C fire damper also regulates flow, it is called a fire control damper.

2. A 3C fire damper linked to a temperature sensor in the ceiling. This type sees little use in China.

3. A 3C fire damper linked to a smoke sensor in the ceiling. This type is often called a smoke control damper.

Where a project needs both, a 3C fire damper may carry both a thermal fuse and a smoke sensor link; such a valve is called a smoke-control 3C fire damper.

In combined systems, a duct may have an exhaust outlet on the main. During smoke extraction that outlet must close; a fire damper combined with a louver outlet, called a fire outlet, serves this.